DSOS User Procedure
Startup
Open the dome
Shutter. This helps the telescope and the chillers (Neslabs) equilibrate at the ambient temperature.
Tip the telescope to ZA = 45°.
UIP> za 45
Connect to the VNC desktop.
mycomp> csovnc.pl -l user dsos
There are three windows on the desktop
The DSOS monitor on the left. The monitor should be running already.
The command window on the lower right.
The agent window on the upper right.
If any of these windows are missing, click on a blank area to display a pop up menu then select the corresponding item to recreate the missing window.
Starting the DSOS monitor also starts the DSOS daemon and server, if necessary.
Initialize the system. In the command window, type
tpick% DSOSinit
This creates the baseline setting for the night.
Initialization should be done with the dome open, at least 1 hour after sunset, and with the telescope at ZA = 45°.
Enable the power supplies.
Display the the power supply page in the status monitor. In the monitor window, type p
.
Enable the power supply outputs. In the command window, type
tpick% DSOSpower on
The power supplies are normally left in standby mode during the day.
On the front panels, the remote light should be illuminated.
If any power supplies are in manual mode,
start them.
Settling.
Depending on the initial toothpick (actuator) displacements, the system needs about 15 min to settle.
The power supply monitor page shows the current demands.
After settling, the current ideally will be 9 A or less for both +15 V (odd) and -15 V (even) power supplies. Under some circumstances, the current may remain higher.
Display the dish status in the status monitor. In the monitor window, type 1
.
System Agent.
In the agent window, type
tpick% DSOSagent
Every 2.5 min, the system agent commands the specific actuator (toothpick) displacements appropriate for the telescope ZA.
Command values and settings are logged in agent.log
.
Shutdown
At the end of observing, stop the DSOS agent. In the agent window, type ctrl-C
.
Return the system to its baseline value. In the command window, type
tpick% DSOSbase
After 10 minutes, disable the power supply outputs. In the command window, type
tpick% DSOSpower off
Please turn off any power supplies that are in manual mode. Leave everything else on.
Disconnect from the VNC desktop.
System checks
During observations, please check the system periodically.
If any thermistor or D/A values are 0.00, the computer will issue a warning.
Is coolant flowing to the dish manifold and to the system racks?
Are any chillers (Neslabs), pumps, or rack fans are not running?
Are any power supply pairs very one sided? For example:
PS1 = 7V / 75.0A
PS2 = 15V / 0.00A
Should any of these faults occur, turn off the power supplies first. Then shut down the rest of the system.
Do not use the DSOS until the fault is repaired.
Left uncorrected, these faults may cause system damage and misadjustment of the dish panels.
Essential. Please notify CSO staff what failed and when.
Troubleshooting
Reinitialization
If the system was initialized during the day before sunset, reinitializing 1 hour after the sunset is worthwhile.
Another reason for reinitialize is a change of more than 5 °C in the ambient temperature since the original initialization.
A significant temperature change in the middle of the night often indicates, however, bad observing weather, so be sure to check for rain or snow. Shutting the dome may be necessary.
It is not recommended to rebaseline often.
Stop the DSOS agent. Type ctrl-C
in the agent window.
Return the system to its baseline value. Type DSOSbase
in the command window.
After 10 minutes, disable the power supply outputs. Type DSOSpower off
in the command window.
Tip the dish to 45° (UIP> za 45
).
Wait 40 minutes for the telescope to equilibrate to ambient temperature.
Start again with the Initialization step above.
Power Supplies
Reset
On occasion, the power supplies get confused, which prevents them from turning on correctly. If this occurs, reset them.
Display the the power supply page in the status monitor. In the monitor window, type p
.
Disable the power supply outputs. Type DSOSpower off
in the command window.
Reset the power supplies. Type DSOSpower reset
in the command window.
Return the power supplies to standby. Type DSOSpower off
in the command window.
Enable the power supply outputs. Type DSOSpower on
in the command window.
Resume the startup procedure.
Do not repeat this procedure more than a couple of times. If it doesn't fix the problem, then something else must be
wrong.
Manual start
In unusual circumstances, power supplies may require manual starts. Power supplies are always operated in pairs.
New style
Turn on both supplies using the switches on the left of their front panels.
Once the supplies stabilize, the panel displays will indicate (close to) zero voltage and current.
Output 0.00 VOLTS
0.0 AMPS
Press the MENU
buttons near the keypad on the right of the front panels.
The displays will indicate the memory locations, 1 ≤ N ≤ 9, and the the correct correct voltage and current settings.
Restore from Memory: N
15.00 V 75.0 A 3000 W
After the proper settings are displayed on both supplies, simultaneously press the ENTER
buttons on the right of the panels. This applies both biases to the power amps at the same time.
The displays will initially indicate something like:
Output 15.00 VOLTS
75.0 AMPS
Repeat for any other pairs of supplies in manual mode.
Old style
Turn on both supplies using the switches on the left of their front panels.
Press ENABLE
on the left side.
Turn off
Turn off supplies using the switches on the left of their front panels.
Coolant
Chillers (Neslabs)
If any of the chillers sounds an alarm, check its error display.
ADD
:
Error 54
:
Press the up and down arrow keys on the front panel simultaneously and hold for 10 seconds until the alarm turns off.
Press the computer control button (picture of a keyboard on the button) so that the light is off.
Turn the chiller off.
Turn the chiller back on. The alarm and error message should be gone.
Any other error:
Pumps
If any of the four pumps supplying the dish manifolds fails, usually the meters will read low (or no) pressure and the pump may be hot to the touch.
Turn off the power supplies.
Close the manifold valves on the failed pump. There are three valves for each pump. Turn them clockwise until they close.
Shut off the power to the failed pump. Either turn off its power strip or unplug the pump from its power strip.
Shut down the rest of the system.
Do not use the DSOS until the pump is repaired or replaced.
Essential. Please notify CSO staff which pump failed and at when.